Programmable Automation Controllers
13-22
APAX-5073
Specifications
General
Certification CE, FCC class A
Dimension (W x H x D) 30 x 139 x 100 mm
Enclosure ABS+PC
Weight 180 g
Connector 2 x RJ-45 (2-channel switch, share same IP
address)
Power Consumption 2 W @ 5 V
DC
(typical)
Communication
Protocol PROFINET RT
Connected I/O Modules 32 (max.)*
Digital Signals 768 (max.)
Analog Signals 192 (max.)
Data Transfer Rates 10/100 Mbps
APAX IO Topology Line or Star
Environment
Operating Temperature -10 ~ 60°C (mounted vertically)
Storage Temperature -40 ~ 85°C
Relative Humidity 5 ~ 95% (non-condensing)
Shock Protection 10 G @ wall mount, half sine, 11 ms
(Confirms to IEC 60068-2-27)
Vibration Protection 1 Grms @ 5 ~ 500 Hz (Random, operating, 1
hr/axis)
2 G @ 5 ~ 500 Hz (Sine, non-operating, 1 hr/
axis)
(Confirms to IEC 60068-2-64 and IEC 60068-2-
6)
Ordering Information
APAX-5071 PROFINET Communication Coupler
Accessories
APAX-5002 2-slot Backplane Module
APAX-5343E Power Supply for APAX Expansion Module
APAX-5071
APAX-5073
PROFINET Communication Coupler
PROFIBUS Communication Coupler
Specifications
General
Certification CE, FCC class A
Dimension (W x H x D) 30 x 139 x 100 mm
Enclosure ABS+PC
Weight 180 g
Connectors DB-9
Power Consumption 2 W @ 5 V
DC
(typical)
Communications
Protocol PROFIBUS-DP
Connected I/O Modules 32 (max.)*
Digital Signals 768 (max.)
Analog Signals 192 (max.)
Data Transfer Rates 12Mbits/s
APAX IO Topology Line or Star
Isolation Protection 2,500 V
AC
Environment
Operating Temperature -10 ~ 60°C (mounted vertically)
Storage Temperature -40 ~ 85°C
Relative Humidity 5 ~ 95% (non-condensing)
Shock Protection 10 G @ wall mount, half sine, 11 ms
(Confirms to IEC 60068-2-27)
Vibration Protection 1 Grms @ 5 ~ 500 Hz (Random, operating, 1
hr/axis)
2 G @ 5 ~ 500 Hz (Sine, non-operating, 1 hr/
axis)
(Confirms to IEC 60068-2-64 and IEC 60068-2-
6)
Ordering Information
APAX-5073 PROFIBUS Communication Coupler
Accessories
APAX-5002 2-slot Backplane Module
APAX-5343E Power Supply for APAX Expansion Module
APAX-5071
RoHS
COMPLIANT
2002/95/EC
RoHS
COMPLIANT
2002/95/EC
*APAX DI/O modules can use ID number 0 ~ 31, while AI/O modules and counter modules can only use ID numbers 0 ~ 15
NEW NEW