Advantech PCL-818 Series Bedienungsanleitung Seite 58

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 74
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 57
PCL-818 Series User Manual 50
C.6 MUX Scan Channel Control — BASE+02H
The write register at BASE+02H controls multiplexer (MUX) scanning.
The high nibble provides the stop scan channel number, and the low nib-
ble provides the start scan channel number. Writing to this register auto-
matically initializes the MUX to the start channel. Each A/D conversion
trigger sets the MUX to the next channel.
With continuous triggering the MUX will scan from the start channel to
the end channel, then repeat. For example, if the start channel is 3 and the
stop channel is 7, then the scan sequence is 3, 4, 5, 6, 7, 3, 4, 5, 6, 7, 3,
4.…
PCL-818L
Input Range Range Code
JP7=5V JP7=10V G1 G0
±5V ±10V 0 0
±2.5V ±5V 0 1
±1.25V ±2.5V 1 0
±0.625V ±1.25V 1 1
Note: G3 and G2 are not used for PCL-818L.