ADAM 4000 Series
3-12
ADAM
ADAM-4012
Analog Input Module
Analog Input
• Effective resolution: 16-bit
• Input type: mV, V or mA
• Input range: ±150 mV, ±500 mV,
±1 V, ±5 V, ±10 V and ±20 mA
• Isolation voltage: 3000 V
DC
• Sampling rate: 10 samples/sec.
• Input impedance: 2 MΩ
• Bandwidth: 2.62 Hz
• Accuracy: ±0.05% or better
• Zero drift: ±6 µV/°C
• Span drift: ±25 ppm/°C
• CMR @ 50/60 Hz: 150 dB
• NMR @ 50/60 Hz: 100 dB
Digital Input
• Channels: 1
Logic level 0: +1 V max.
Logic level 1: +3.5 V ~ +30 V
Pull up current: 0.5 mA,
10 KΩ resistor to +5 V
• Event counter:
Max. input frequency: 50 Hz
Min. input pulse width: 1 msec.
Digital Output
• Channels: 2
Open collector to 30 V,
30 mA max. load
Power dissipation: 300 mW
Built-in Watchdog Timer
Power
• Power requirements:
+10 to +30 V
DC
(non-regulated)
• Power consumption: 1.2 W
ADAM-4011D
Thermocouple Input
Module with LED Display
Analog Input
• Effective resolution: 16-bit
• Input type: Thermocouple, mV, V or
mA
• Input range: same as ADAM-4011
• T/C type and temperature range:
same as ADAM-4011
• Isolation voltage: 3000 V
DC
• Input surge protection: Yes
• Thermocouple open detection: Yes
• Sampling rate: 10 samples/sec.
• Input impedance: 2 MΩ
• Bandwidth: 2.62 Hz
• Accuracy: ±0.05% or better
• Zero drift: ±3 µV/°C
• Span drift: ±25 ppm/°C
• CMR @ 50/60 Hz: 150 dB
• NMR @ 50/60 Hz: 100 dB
Display
• LED indicator: 4½ - digit readout
Digital Input
• Channels: 1
(See specifications of ADAM-4012)
• Event counter:
(See specifications of ADAM-4012)
Digital Output
• Channels: 2
(See specifications of ADAM-4012)
Built-in Watchdog Timer
Power
• Power requirements:
+10 to +30 V
DC
(non-regulated)
• Power consumption: 1.4 W
ADAM-4011 Analog Input Module
ADAM-4011D Thermocouple Input Module
with LED Display
ADAM-4012 Analog Input Module
ADAM-4011
Analog Input Module
Analog Input
• Effective resolution: 16-bit
• Input type: Thermocouple, mV, V or mA
• Input range: ±15 mV, ±50 mV, ±100 mV,
±500 mV, ±1 V, ±2.5 V, ±20 mA
• T/C type and temperature range:
J 0 ~ 760° C
K 0 ~ 1370° C
T -100 ~ 400° C
E 0 ~ 1000° C
R 500 ~ 1750° C
S 500 ~ 1750° C
B 500 ~ 1800° C
• Isolation voltage: 3000 V
DC
• Input surge protection: yes
• Sampling rate: 10 samples/sec.
• Input impedance: 2 MΩ
• Bandwidth: 2.62 Hz
• Accuracy: ±0.05% or better
• Zero drift: ±3 µV/°C
• Span drift: ±25 ppm/°C
• CMR @ 50/60 Hz: 150 dB
• NMR @ 50/60 Hz: 100 dB
Digital Input
• Channels: 1
(See specifications of ADAM-4012)
• Event counter:
(See specifications of ADAM-4012)
Digital Output
• Channels: 2
(See specifications of ADAM-4012)
Built-in Watchdog Timer
Power
• Power requirements:
+10 ~ +30 V
DC
(non-regulated)
• Power consumption: 1.2 W