Advantech RS-485 Bedienungsanleitung Seite 156

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 348
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 155
6-34 ADAM-5000
Command Set
$aaSi0 $aaSi0
Name RTD Span Calibration
Description Calibrates a specified RTD input module of a specified
system to correct for gain errors.
Syntax $aaSi0(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system which contains the
RTD module.
Si identifies the slot i (i:0 to 3) containing the RTD
module to be calibrated.
0 represents the span calibration command.
(cr) is the terminating character, carriage return (0Dh).
Response. !aa(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error
or communication error or if the specified address does
not exist.
> delimiter character indicating a valid command was
received.
? delimiter character indicating the command was
invalid.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
(cr) is the terminating character, carriage return (0Dh).
5013 RTD Input